Global Distributor Network
Pyroplex Golbal Distributers
 Acrylic Sealant - 4 Hour Fire RatedDownload PdfDownload Pdf

Pyroplex Intumescent Acrylic Sealant is a one part, high modulus, halogen free product. It is suitable for perimeter pointing around doors and windows and sealing small openings and pipe penetrations which have been protected by the recommended Pyroplex Intumescent product. It is also ideal for sealing around trunking and steel pipes.

Pyroplex Intumescent Acrylic Sealant is fire rated up to 4 hours and offers excellent adhesion to many common building substrates and is also fully paintable.

Pyroplex Intumescent Acrylic Sealant is tested to BS EN1366: Part 4: 2006 and other international standards including BS476.
Intumescent Acrylic Sealant
Field of Application
Pyroplex Intumescent Acrylic Sealant has been specifically designed for use when:
• Sealing linear gap joint seals.
• Sealing small openings in fire walls and floors.
• Sealing around plastic pipe or cable penetrations which have been protected with the recommended Pyroplex Intumescent product eg. pipe collar, pipe wrap, linear gap seal.
• Sealing around trunking and steel pipes.

Product Features
• Fire rating up to 4 hours.
• Excellent adhesion to many common building substrates.
• Joint movement accommodation +/-15%.
• Expands by approximately 15% in fire conditions.
• Fully paintable.
• Available in white. Other colours also available subject to a minimum order quantity.

Product Data
Ref. Seal Width Joint Type Backing
Media
Integrity Insulation
A 30mm Single PE 240min 71min
B 30mm Double MW 240min 240min
C 10mm Single PE 240min 180min
D 10mm Double MW 240min 240min
I 20mm Single PE 240min 90min
K 20mm Double MW 240min 240min

Backing Materials
PE Polyethylene, with a nominal density of 0.35kg/m3
MW Mineral wool, with a nominal density of 100kg/m3


Product Packaging
Pyroplex Silicone Sealant is supplied in 310ml cartridges. 25 cartridges per box complete with 25 nozzles.
  Product Testing
Pyroplex have carried out numerous independent fire resistance tests to confirm the suitability of the product and to demonstrate product compliance by utilising BS EN1366: Part 4:2006 and other international standards including BS476. WF Report No. 166576A is available upon request.

Installation Instructions
Ensure that all the surfaces are clean, dry, sound and free frost (external application) clean all joints thoroughly to ensure that the adhesion of the silicone to the substrate is not impaired.

It may be necessary to mask adjacent areas to prevent contamination and to ensure a neat sealant line. Masking tapes should be immediately removed after tooling and finishing.

Install backing materials as required and commence to fill the cavity or void with silicone.

The joint should be tooled within 5 minutes of the application to ensure good a contact between the silicone and substrate. Tooling of the sealant also gives a smooth and professional finish.

Excess material should be cleaned off non-porous surfaces using a suitable solvent. Sealant on porous surfaces should be left until cured and excess removed by mechanical means.

Dispose of spent cartridges in accordance with local regulations.

Copyright Pyroplex 2008

Email:info@pyroplex.com