Field
of Application
Pyroplex pipe wraps
have been specifically designed to prevent the passage of fire and hot
gases through:
• Concrete and masonry walls.
• Concrete floor constructions.
• Soil, waste and drainage ‘above ground’
applications.
Product
Features
•Wraps
have achieved a fire rating of either 2 hour or 4 hour.
•Wraps are easy to place around pipe and slide into position.
• Intumescent material is totally unaffected by water, is
robust, ‘non-flaking’and difficult to tear.
Product
Testing
Pyroplex
have carried out numerous independent fire resistance tests to confirm
the suitability of the product and to demonstrate product compliance by
utilising BS476: Part 20 1987 and other international standards.
The reports have been consolidated in Assessment Report No. FEA/F98172
& this is available on request from Pyroplex Limited.
|
|
Product Range
2 Hour Fire Rated Pipe Wrap
| Part Number |
Fire Rating |
Pipe
Diameter |
Dia.Hole
Wall/Floor |
| PPW55-2 |
2 Hours |
55 |
70 |
| PPW82-2 |
2 Hours |
82 |
98 |
| PPW110-2 |
2 Hours |
110 |
130 |
| PPW160-2 |
2 Hours |
160 |
190 |
2
Hour Fire Rated PipeWrap
| Part Number |
Fire Rating |
Pipe
Diameter |
Dia.Hole
Wall/Floor |
| PPW55-4 |
4 Hours |
55 |
70 |
| PPW82-4 |
4 Hours |
82 |
98 |
| PPW110-4 |
4 Hours |
110 |
130 |
| PPW125-4 |
4 Hours |
125 |
155 |
| PPW160-4 |
4 Hours |
160 |
190 |
Note: