CE Marked Pipe Collar 200 Series

CE Marked Pipe Collar 200 Series

CE Marked 200 Series Pipe Collar

Application: Service penetrations – plastic SWD systems
Fire Resistance Period: 120 minutes
Insulation/integrity: Insulation and integrity
Test Standard: BS 476: Part 20: 1987 and BS EN 1366-3: 2009
Approval Type: Certifire CF635 / CE Mark 1121-CPD-JA5002

Pyroplex® CE Marked 200 Series Pipe Collars have been specifically designed to re-instate the fire resistance of a wall or floor which has been penetrated by plastic flammable pipes
used in soil, waste and drainage services.

They will seal closed flammable pipes from 55mm to 160mm diameter and can be face fixed to a wall or ceiling structure. They are suitable for use on concrete and masonry partitions.

Pyroplex® CE Marked 200 Series Pipe Collar is tested to BS 476: Part 20: 1987 and BS EN 1366-3: 2009 and has a European classification in accordance with BS EN 13501-2: 2007. Pyroplex® Pipe Collars are compliant with the requirements given in CERTIFIRE TS03.

Testing & Certification

CE Marking

EC Certificate of Conformity 1121-CPR-JA5002

European Technical Approval ETA – 15/0136

Test Standard

BS 476: Part 20: 1987

BS EN 1366-3: 2009

Approval Type

Certifire TS03 Certificate No. CF635

PSB Approval- CLS1A 16 03 95058 005

PSB Approval- CLS1A 16 02 95058 004

  • A fire resistance of up to 120 minutes.
  • 200 series collars have a galvanised steel outer casing.
  • Tab closing device means collars are easy to fix in place around pipe and rotate or slide into position.
  • Intumescent material is totally unaffected by water, is robust, ‘non-flaking’ and difficult to tear.

Pyroplex® CE Marked 200 Series Pipe Collar has been specifically designed to prevent the passage of fire and hot gases through:

  • Concrete and masonry partitions.
  • Soil, waste and drainage ‘above ground’ applications.

Range for concrete and masonry walls and floors

Part NoPipe materialsPipe diameter [mm]Pipe wall thickness [mm]Collar depth [mm]No. of fixing lugsWallFloor
PPC55-2PVC-u553.2603EI120EI120
PPC75-2PVC-u753.2603EI120EI120
PPC82-2PVC-u823.2603EI120EI120
PPC110-2PVC-u1103.2604EI120EI120
PPC160-2PVC-u1603.2606EI120EI120

All measurements are shown in millimetres [mm].

1. Ensure substrate around pipe is flat and free from obstructions – if necessary make good by using Pyroplex® Intumescent Acrylic Sealant around the perimeter.
2. Release retaining pin and position pipe collar around pipe.
3. Slide the tab through slot in pipe collar and fold back 180˚ to secure.
4. Secure pipe collar by drilling holes in structure by using fixing lugs as template. To fix use M8 x 65mm sleeve anchors or 50mm [minimum] expanding bolts. Do not use plastic raw
plugs and or plastic sleeve anchors.

5. When the collar has been securely fitted into place any residual gaps between the collar and the substrate can be filled using Pyroplex® Intumescent Acrylic Sealant.

 
Pipe-Collars-Installation-1
Pipe-Collars-Installation-2
Pipe-Collars-Installation-3
Pipe-Collars-Installation-4
Pipe-Collars-Installation-5

Pyroplex® Limited have carried out numerous independent fire resistance tests to confirm the suitability of the product and to demonstrate product compliance by utilising BS 476: Part 20: 1987 and BS EN 1366-3: 2009. EN Classification report to BS EN 13501-2: 2007 is available to download.

Providing the product is installed in accordance with the requirements of the guidance document the product is guaranteed for a period of 10 years.

Pyroplex

Pyroplex